| 型號名稱 | | 型號代碼 | | 敏感元件 | | 阻值表 | | 長度 | | 注釋 | |
| | | | | | | | | | |||
| | | | | | | | | | | | |
| SD-Tn3-12 | 40-20 0014 | | NTC 3k? at 25°C | | B25/50 3935 | | 120mm (4.7) | | | | |
| | | | | | | | | | | | |
| SD-Tn10-12 | | 40-20 0002 | | NTC 10k? at 25°C | | B25/50 3935 | | 120mm (4.7) | | Vector standard | |
| SD-Tn11-12 | 40-20 0015 | | NTC 10k? at 25°C | | B25/50 3630 | | 120mm (4.7) | | | | |
| SD-Tn20-12 | 40-20 0016 | | NTC 20k? at 25°C | | B25/50 4200 | | 120mm (4.7) | | | | |
| SD-Tn100-12 | 40-20 0017 | | NTC 100k? at 25°C | | B25/50 4200 | | 120mm (4.7) | | | | |
| SD-Tp1-12 | 40-20 0023 | | PT100 | | EN60751 | | 120mm (4.7) | | | | |
| SD-Tp2-12 | 40-20 0024 | | PT1000 | | EN60751 | | 120mm (4.7) | | | | |
| | | | | | | | | | | | |
| SD-Tk5-12 | 40-20 0025 | | NI1000 | | 5000 ppm/K | | 120mm (4.7) | | | | |
| | | | | | | | | | | | |
| SD-Tn3-20 | 40-20 0018 | | NTC 3k? at 25°C | | B25/50 3935 | | 200mm (7.9) | | | | |
| | | | | | | | | | | | |
| SD- Tn10-20 | | 40-20 0003 | | NTC 10k? at 25°C | | B25/50 3935 | | 200mm (7.9) | | Vector standard | |
| SD- Tn11-20 | 40-20 0020 | | NTC 10k? at 25°C | | B25/50 3630 | | 200mm (7.9) | | | | |
| SD- Tn20-20 | 40-20 0021 | | NTC 20k? at 25°C | | B25/50 4200 | | 200mm (7.9) | | | | |
| SD- Tn100-20 | 40-20 0022 | | NTC 100k? at 25°C | | B25/50 4200 | | 200mm (7.9) | | | | |
| | | | | | | | | | | | |
| SD- Tp1-20 | 40-20 0026 | | PT100 | | EN60751 | | 200mm (7.9) | | | | |
| SD- Tp2-20 | 40-20 0027 | | PT1000 | | EN60751 | | 200mm (7.9) | | | | |
| | | | | | | | | | | | |
| SD- Tk5-20 | 40-20 0028 | | NI1000 | | 5000 ppm/K | | 200mm (7.9) | | | | |
| | | | | | | | | | | | |
附件 | | | | | | | | | | | | |
與 AMI 配套使用可以測量管道內(nèi)溫度. | | | | | | | | | | |||
| 型號名稱 | | 型號代碼 | | | | 描述 | | 長度 | | | |
| | | | | | | | | | | ||
| | | | | | | | | | | | |
| AMI-S5 | 40-50 0007 | | | | | | 50mm (2.0) | | | | |
| AMI-S7 | 40-50 0008 | | | | 不銹鋼 | | 75mm (3.0) | | | | |
| AMI-S10 | 40-50 0009 | | | | | | 100mm (3.9) | | | | |
| AMI-S15 | 40-50 0010 | | | | | | 150mm (5.9) | | | | |
| | | | | | | | | | | | |
安裝 探測器應(yīng)直接安裝在管道上,在此位置內(nèi)能很好的測量混合的空氣。安裝的位置應(yīng)該距風(fēng)機(jī)的出風(fēng)口有兩三米。
安裝在回風(fēng)風(fēng)道上,安裝位置可以在回風(fēng)風(fēng)道任意處,一般在接近空調(diào)箱的回風(fēng)風(fēng)道上。
在風(fēng)道上開一個(gè) 8mm 的孔,然后把溫度傳感器探針插入到風(fēng)道里面。用 2 個(gè) 10mm 長的自攻螺絲 將外殼牢固的固 定在風(fēng)道上。 安裝水路管道上,需要焊接一個(gè) G1/2 的內(nèi)螺紋管箍。把 AMI 附件直接擰入管箍內(nèi),然后插入傳感器 安裝接線需要按照接線圖: 這個(gè)傳感器需要兩個(gè)線,通常用 1mm²的非屏蔽的雙絞線